Analog signals 4–20 mA, 0–20 mA, 0–10 V

Standard current and voltage signals, live zero, wire-break detection, NAMUR NE 43 failure levels and typical wiring mistakes.

Standard signals

SignalZeroFull scaleNotes
4–20 mA4 mA20 mAlive zero, loop-powered 2-wire transmitters, HART
0–20 mA0 mA20 mAa broken wire is indistinguishable from a zero reading
0–10 V0 V10 Vshort runs, sensitive to voltage drop and noise
1–5 V1 V5 Vvoltage live zero, often a 250 Ω shunt on 4–20 mA
±10 V−10 V+10 Vdrive speed references, servo amplifiers

A current signal is insensitive to line resistance within the allowed load: the source maintains the current regardless of cable length. That is why field transmitters use 4–20 mA, while voltage is used for short connections inside a cabinet.

Live zero

With 4–20 mA the bottom of the measuring range is 4 mA, not 0. A current near zero does not mean "zero value" but a fault: broken wire, no transmitter supply, blown fuse. The wire-break diagnostic of Siemens S7-1500 analog modules can only be configured for the 4–20 mA and 1–5 V ranges — precisely because these have a live zero.

A 2-wire transmitter is powered by the loop itself: 4 mA is roughly the minimum current at which its electronics keep running.

NAMUR NE 43

The NAMUR NE 43 recommendation separates measurement information from a transmitter's failure signal:

CurrentMeaning
3.8 … 20.5 mAmeasurement (slightly beyond 4…20 mA allowed)
≤ 3.6 mAdownscale failure signal
≥ 21.0 mAupscale failure signal
3.6 … 3.8 and 20.5 … 21.0 mAundefined zone

The failure direction (down or up) is usually selectable in the transmitter. The PLC must distinguish "value out of range" from "transmitter reports a failure" and must not use a failure value in control or interlocks.

Wiring 2-, 3- and 4-wire transmitters

  • 2-wire (passive) — supply and signal on one pair; the input must be configured to match (whether it powers the loop).
  • 3-wire — separate supply wire, common negative.
  • 4-wire (active) — own supply, current output acts as a source.

A common mistake is two supplies in one loop, or none: in the first case the current saturates, in the second the input sees 0 mA ("wire break").

Typical faults

SymptomPossible cause
~0 mAbroken wire, no loop supply, wrong transmitter type (2-/4-wire) configured
steady 20.5…22 mAtransmitter in failure state (NE 43) or overrange
value driftsnoise, shield grounded at both ends, poor contact
about 20 % of range at zero process valuewrong range in module configuration (0–20 instead of 4–20)

Tools

Loading the map…

Sources

  1. SIMATIC S7-1500, ET 200MP, ET 200SP, ET 200AL, ET 200pro Analog value processing — Function Manual 06/2014 — Siemens AG
  2. NAMUR Recommendations and Worksheets (NE 43) — NAMUR