IO-Link: smart sensors on a point-to-point link

IO-Link (IEC 61131-9) connects one sensor or actuator to a master port over a standard 3-wire cable: process data, parameters, IODD files and device replacement.

Idea

IO-Link is not a fieldbus but a point-to-point serial link between an IO-Link master port and one device (sensor, actuator, valve terminal, small I/O hub). The master sits on PROFINET, EtherNet/IP, EtherCAT or a PLC backplane and passes data upward.

Physical layer

  • Standard unshielded 3- or 5-wire sensor cable, M12/M8 connectors, up to 20 m.
  • Pin 4 (C/Q) carries IO-Link communication or works as a normal switching signal (SIO mode) — an IO-Link sensor can replace a plain one.
  • Port class A: pin 2 free or extra DI/DO; class B: additional galvanically separated actuator supply on pins 2/5.
  • Transmission rates: COM1 4.8, COM2 38.4, COM3 230.4 kbit/s — chosen by the device.

Data

TypeUse
Process dataCyclic values (e.g. distance + switching state), a few bytes
Service data (ISDU)Parameters addressed by index/sub-index, read/write on demand
EventsDiagnostics such as overtemperature, short circuit

Every device is described by an IODD (IO Device Description, XML) with its parameters, process data layout and texts.

Why engineers like it

  • Parameters (switch points, filters, units) are set from the PLC or a tool instead of buttons on the sensor.
  • Data storage: the master keeps a copy of the parameters; a replaced device of the same type receives them automatically.
  • Diagnostics reach the PLC instead of only an LED.

Typical issues

Wrong process data mapping (byte order inside the IO-Link process data), using a class A port where class B power is needed, and validation settings (vendor/device ID) that reject a replacement device of another revision.