What is a PLC: architecture, I/O and memory

The parts of a programmable logic controller — CPU, memory areas, digital and analog I/O, communication modules and remote I/O — and what they mean for design and troubleshooting.

Components

PartRole
CPUExecutes the user program cyclically, holds the process image, runs communication
Power supplyUsually 24 V DC for CPU and modules; separate load supply for outputs
Digital inputs (DI)Read 24 V DC (or 230 V AC) signals: buttons, limit switches, sensors, contacts
Digital outputs (DO)Switch relays, contactor coils, lamps, valves — transistor (fast, DC) or relay (AC/DC, slow, limited cycles)
Analog inputs (AI)4–20 mA, 0–10 V, RTD, thermocouple → digital value (e.g. 0…27648)
Analog outputs (AO)Speed references, valve positions
CommunicationIntegrated Ethernet ports, fieldbus masters (PROFIBUS, CAN), serial modules
Remote I/OI/O stations near the machine connected by a fieldbus (PROFINET, EtherNet/IP, EtherCAT)

Compact PLCs integrate CPU and some I/O in one housing; modular systems mount modules on a rail or rack. Safety PLCs (F-CPUs) run additional certified safety programs and use safety I/O modules.

Memory

  • Load memory — the downloaded project (often on a memory card).
  • Work memory — code and data used during execution.
  • Retentive memory — data kept after power off (counters, operating hours, recipes). See retentive data and startup.

Digital I/O wiring: sinking and sourcing

With 24 V DC sourcing (PNP) devices, the sensor switches +24 V to the input; with sinking (NPN) devices it switches 0 V. Input modules are built for one type (or are configurable); mixing them without care gives inputs that never switch. See discrete sensors.

Choosing I/O

  • Count signals per type plus 10–20 % spare.
  • Check output current per channel and per module group, and inductive load protection.
  • Consider diagnostics (wire break, short circuit) and channel isolation for analog signals from different sources.
  • Place remote I/O close to the field to save cable, but keep safety and critical signals on reliable paths.