DP Flow (√ΔP) Calculator

Meter

Calculate from

Q = Qmax · √(ΔP / ΔPmax) at constant density and discharge coefficient. 10 % flow is only 1 % of ΔP — this is why a low-flow cut-off is used and why the turndown of DP meters is limited.

Flow ↔ ΔP ↔ mA

Flow, %ΔP, %mA (linear ΔP)mA (√ extracted)
0044
50.254.044.8
1014.165.6
2044.647.2
256.2558
3095.448.8
40166.5610.4
5025812
60369.7613.6
704911.8415.2
7556.251316
806414.2416.8
908116.9618.4
1001002020

PLC code (linear ΔP transmitter)

1(* Q = Qmax * SQRT(dP / dPmax); low-flow cut-off 2.0 % of flow *)
2IF DP_Pct <= 0.0 THEN
3 Flow := 0.0;
4ELSE
5 Flow := 1.0 * SQRT(DP_Pct / 100.0);
6END_IF;
7IF Flow < 0.02 THEN
8 Flow := 0.0;
9END_IF;