Retentive data, startup behaviour and fault handling

What survives a power failure, what happens on warm and cold restart, first-scan initialization, startup in a safe state, PLC fault reactions and simulation for testing.

Retentive vs non-retentive

DataShould it be retentive?
Operating hours, start counters, totalsYes
Setpoints entered by operators, recipesYes (or stored in HMI/SCADA)
Sequence states, run commandsUsually no — the plant must not restart by itself after power returns
Alarm latches of tripsDepends; safer to re-evaluate from the field

IEC 61131-3 declares VAR RETAIN; TwinCAT and CODESYS also offer PERSISTENT (kept across a new download). Siemens S7-1500 marks retentivity per variable in data blocks.

Startup

Controllers distinguish warm restart (retentive data kept, non-retentive initialized) and cold restart / reset (everything initialized). Use a startup routine (Siemens startup OB 100, a FirstScan flag in CODESYS/TwinCAT) to:

  • put sequences into an idle state;
  • require a new operator command before equipment starts;
  • check plausibility of retentive values;
  • wait until communication and remote I/O are up before evaluating their signals.

Fault reactions

PLCs call error handlers or go to STOP on serious errors (cycle time exceeded, I/O access errors, division by zero in some systems). Decide deliberately: stopping the CPU sets outputs to their substitute values — is that the safe state of the plant? Remote I/O stations have their own output behaviour on communication loss (switch off, hold last value, substitute value) that must match the process.

Simulation

Build a simulation mode into equipment blocks (feedback follows command after a delay, analog values from a simple model). It allows testing sequences on PLCSIM, a soft PLC or a test bench before the plant exists — and must be impossible to activate unnoticed in production.