Ideal, parallel and series PID forms

Three ways to write one controller: equations, conversion between them and its limits (Ti ≥ 4·Td for the series form, Kp = 0, signs). Why settings cannot be copied between blocks without checking the form.

In short. The same setting can be written in three ways, with different numbers. Before entering parameters into a PLC block you need to know which form it computes — otherwise Kc, Ti and Td do not mean what you calculated. The parameter converter does the conversion.

idealKc1 + 1/(Ti·s) + Td·sparallelKpKi/sKd·sΣseriesKc′1 + 1/(Ti′·s)1 + Td′·s
The same controller written three ways. Ideal: one gain Kc multiplies all three actions. Parallel: independent gains. Series: a PI and a PD part in a row (interacting).

Equations

Error e = SP − PV, time in seconds.

Ideal (ISA, standard, "dependent"):
    u = Kc · [ e + (1/Ti)·∫e dt + Td·de/dt ]

Parallel (independent):
    u = Kp·e + Ki·∫e dt + Kd·de/dt

Series (interacting):
    U(s) = Kc′ · (1 + 1/(Ti′·s)) · (1 + Td′·s) · E(s)
FormParametersFeature
IdealKc, Ti, TdKc multiplies all three actions: changing Kc changes I and D too
ParallelKp, Ki (1/s), Kd (s)each gain changes only its own term
SeriesKc′, Ti′, Td′PI and PD parts in a row; historically pneumatic and analog controllers

NI describes exactly these three classes and stresses that there is no industry-wide standard. MathWorks calls the two forms of its block "ideal" and "parallel"; in the MathWorks ideal form the parameter I is 1/Ti, not Ti.

Conversion

Ideal ↔ parallel (always possible when Ti > 0):

Kp = Kc        Ki = Kc / Ti        Kd = Kc · Td
Kc = Kp        Ti = Kp / Ki        Td = Kd / Kp

Series → ideal (always possible):

Kc = Kc′ · (Ti′ + Td′) / Ti′        Ti = Ti′ + Td′        Td = Ti′·Td′ / (Ti′ + Td′)

Ideal → series — only when Ti ≥ 4·Td:

r = √(1 − 4·Td/Ti)
Kc′ = Kc·(1 + r)/2        Ti′ = Ti·(1 + r)/2        Td′ = Ti·(1 − r)/2

With Ti < 4·Td the ideal controller has complex zeros, which a series controller cannot reproduce. This is a structural limit, not a numerical one.

Example

Ideal form: Kc = 2.5, Ti = 40 s, Td = 4 s.

FormParameters
ParallelKp = 2.5; Ki = 0.0625 1/s; Kd = 10 s
SeriesKc′ = 2.218; Ti′ = 35.49 s; Td′ = 4.508 s (Ti = 40 ≥ 4·4 = 16, conversion possible)
Proportional bandPB = 100/2.5 = 40 % (only for a normalised Kc)

Open the example in the converter

Check back: Kc = 2.218·(35.49 + 4.508)/35.49 = 2.5; Ti = 35.49 + 4.508 = 40.0 s.

When conversion is impossible

SituationWhy
Parallel form with Kp = 0 and Ki ≠ 0 or Kd ≠ 0the ideal form factors Kc out; with Kc = 0, I and D vanish too
Ki or Kd of opposite sign to Kpit would need a negative Ti or Td
Ideal → series with Ti < 4·Tdcomplex zeros
Integral off (Ti = ∞, Ki = 0)converts: Ki = 0; in the series form Ti′ is off as well

Typical mistakes

  • Entering the ideal Kc as the parallel Kp without converting Ki, Kd. With Kc = 2.5 and Ti = 40 s the parallel Ki is 0.0625 1/s; entering "Ki = 40" makes the integral action 640 times stronger.
  • Confusing Ti and 1/Ti (reset rate) or seconds and minutes — see Kp, Ki, Kd, Ti, Td and PB.
  • Missing that the block filters D and sets it through N. The meaning of N depends on the form: in the ideal form Tf = Td/N, in the MathWorks parallel form Tf = 1/N — see D filter.

Limits

The formulas describe a continuous controller without filter, limits or set-point weighting. Real blocks add sampling, a D filter, P and D on measurement; this changes the behaviour but not the relations between Kc, Ti, Td and Kp, Ki, Kd. Check the correspondence to a particular block (Siemens, CODESYS, OWEN, …) against the documentation of its version.

Loading the map…

Sources

  1. NI — How To Convert PID Parameters From Gain to Time (updated 2023-10-27) — NI (Emerson)
  2. MathWorks — PID Controller block: parallel and ideal forms, filter coefficient N (R2026b) — MathWorks
  3. Åström & Murray — Feedback Systems, 2nd ed. (2020), ch. 11 «PID Control», §11.5 Implementation — Caltech / Lund University