How a control loop works

SP, PV, controller output, error, process and feedback: what a loop is made of, why it works and what breaks it in practice. Conventions of the whole PID section.

In short. A control loop is a controller, a process and a measurement closed into a ring: the controller compares the set point with the measurement and changes the action on the process until they agree. Useful for naming signals correctly in a PLC project and for understanding what PID tuning actually adjusts.

SP+−ePID controlleru (MV)Processvalve → heater → Tdisturbance dPVmeasurement (sensor, transmitter, AI scaling)e = SP − PV
The loop: the controller compares SP with the measured PV and changes the output u until the error e disappears.

Loop signals

SymbolMeaningExample (water heated by steam)Units
SP (set point)desired value65 °CPV units
PV (process variable)measured value of the controlled variable63.4 °C from the sensorPV units
e (error)e = SP − PV1.6 °CPV units
u, MV, CV, OUT (controller output)command to the actuatorvalve 48 % open%, mA, Hz…
d (disturbance)anything that changes PV besides the controllercold-water flow, steam pressure—

Systems call the output MV (manipulated variable), CV (control variable) or OUT. This section uses u and avoids "CV": some packages use CV for the controlled, not the manipulated variable.

Why it works

The controller does not know an exact model of the process. It only sees the error and acts to reduce it. If PV is below the set point the steam valve opens a little; the temperature rises, the error shrinks and the valve movement slows down. This is negative feedback: the controller output opposes the deviation.

Feedback also compensates what nobody accounted for in advance: a change in water flow, fouling of the heat exchanger, drifting steam pressure. The price is that the controller reacts only after the deviation shows up in PV.

Open and closed loop

  • Open loop (manual, MAN): the operator sets the output, the controller is not involved. Step tests are made in this mode — you watch how the process answers a change of the output. See step test and FOPDT model.
  • Closed loop (automatic, AUTO): the controller computes the output. The behaviour depends both on the process and on the settings — this is what you judge from the step response.

Process properties that decide the tuning

PropertyMeaningEffect
Process gain Khow much PV changes per unit of output at steady statethe larger K, the smaller the controller gain must be
Time constant τhow slowly PV moves to its new valuea slow process tolerates stronger integral action
Dead time θtime before PV reacts at allthe main limit on loop speed
Non-linearity, saturationK and τ depend on the operating point; output limited to 0…100 %one set of settings does not fit every operating point; windup protection is needed

Details: FOPDT model and when it does not fit.

Conventions of the "PID control" section

All articles of this section and all PID tools of the application use the same conventions:

  • error: e = SP − PV;
  • controller form: ideal (ISA) u = Kc·[e + (1/Ti)·∫e dt + Td·de/dt] unless stated otherwise (PID forms);
  • time: seconds unless marked "min";
  • normalisation: gains are given with units; a dimensionless Kc means % of output per % of PV range (normalisation);
  • sign: a positive Kc with e = SP − PV is reverse action (direction of action);
  • the process gain K (ΔPV/Δu) and the controller gain Kc (Δu/Δe) are different quantities and are never mixed;
  • derivative filter: time constant Tf in seconds; N is always given together with its form (D filter).

Example

The model used for the examples of this section: heating with K = 1.8 °C/%, τ = 45 s, θ = 12 s. A PI controller with Kc = 1.04 %/°C, Ti = 45 s (SIMC tuning) brings PV to a 1 °C set-point step with 5.5 % overshoot in 74 s (±2 % band).

Open the example in the simulator

Typical mistakes

  • The error is computed as PV − SP while the controller was tuned with formulas for SP − PV: the loop runs away. Check the block's convention.
  • The controller works on an unfiltered or wrongly scaled PV: the settings seem to "drift" while the problem is the measurement.
  • The actuator hits its limit (valve 100 %): the controller cannot do more while the integrator keeps accumulating — see saturation and anti-windup.

Limits

The picture describes one loop with one input and one output. Interacting loops, cascades and feedforward are separate structures: cascade, feedforward, split range.

Loading the map…