Kp, Ki, Kd, Ti, Td and proportional band: units and conventions

Dimensions of PID parameters, seconds and minutes, integral time and reset rate (repeats/min), gain and proportional band. A table of typical mistakes when moving settings between systems.

In short. The same controller is described by different numbers in different systems: Ti in seconds or minutes, integral action as a time or as a rate, gain as a gain or as a proportional band. A wrong convention changes the integral action 60 times or makes the controller 4 times "softer". Before moving settings write down the conventions of the source and of the target.

Parameters and units

Section conventions: e = SP − PV, ideal form (forms).

ParameterFormMeaningUnits
Kcideal, seriescontroller gainoutput unit / PV unit, or %/% when normalised
Tiidealintegral time, "time per repeat"s or min (per repeat)
Tdidealderivative times or min
Kpparallelproportional gainas Kc
Kiparallelintegral gain = Kc/Ti(output unit / PV unit) · 1/s
Kdparallelderivative gain = Kc·Td(output unit / PV unit) · s
Reset rateideal1/Ti, "repeats per minute"repeats/min or repeats/s
PBidealproportional band = 100 % / |Kc|%

Integral time and reset rate

Ti is the time in which, at constant error, the integral term repeats the proportional term. The reset rate is the number of such repeats per unit of time:

reset rate [repeats/min] = 1 / Ti [min]

Example: Ti = 40 s = 0.667 min → 1.5 repeats/min. The effect is opposite: larger Ti — weaker integral; larger reset rate — stronger integral.

Proportional band

PB is the percentage of the PV range that drives the output over 100 % of its range:

PB [%] = 100 / |Kc|        (Kc normalised, %/%)

NI gives the example: a PB of 50 % is a gain of 2. PB has no sign: the direction of action is set separately (direct and reverse action). The formula applies only when input and output are normalised to their ranges; for Kc in °C/% or mA/bar PB is undefined — first convert Kc to %/% (normalisation).

Example: one controller in different conventions

Ideal form Kc = 2.5 %/%, Ti = 40 s, Td = 4 s.

ConventionValues
Kc, Ti, Td in seconds2.5; 40 s; 4 s
Kc, Ti, Td in minutes2.5; 0.6667 min; 0.0667 min
Kc, reset rate2.5; 1.5 repeats/min
PB, Ti, Td40 %; 40 s; 4 s
Kp, Ki, Kd (seconds)2.5; 0.0625 1/s; 10 s
Kp, Ki, Kd (minutes)2.5; 3.75 1/min; 0.1667 min

Check in the converter — switch the time unit and the way the integral is entered.

Typical transfer mistakes

MistakeConsequenceFactor
Ti in minutes entered as secondsintegral stronger×60
Ti in seconds entered as minutesintegral weaker÷60
Reset rate entered into the Ti (min) field1.5 repeats/min becomes "Ti = 1.5 min" instead of 0.667 min — integral weaker÷2.25
PB entered as KcPB 40 % → "Kc = 40" instead of 2.5×16
Ki in 1/min entered as 1/sintegral stronger×60
Kc in engineering units entered into a %/% blockdepends on the rangessee normalisation
Parallel Kd entered as ideal TdD stronger×Kc

How to check settings after moving them

  1. Write down form, time unit, how the integral is entered and the normalisation of the source and of the target.
  2. Convert in the converter: enter in the source form, compare with the target form.
  3. Check one value by hand, e.g. Ki = Kc/Ti.
  4. For new settings on a running plant start with a reduced Kc and watch the trend (manual tuning).

Limits

Parameter names in blocks are not standardised: "Gain", "P", "Kp" can mean Kc or Kp; "Integral" can be Ti, Ki or a reset rate. Find the meaning in the documentation of the particular block and version, not from the field name.

Loading the map…

Sources

  1. NI — How To Convert PID Parameters From Gain to Time (updated 2023-10-27): PB 50 % = gain 2, Ki = Kc/Ti, Kd = Kc·Td — NI (Emerson)