Limits of the FOPDT model

When a first-order-plus-dead-time model fits and when it does not: integrating and oscillatory processes, inverse response, non-linearity, lag-dominant processes. Skogestad's half rule and the integrating process model.

In short. FOPDT describes a self-regulating process with a smooth S-shaped response. If PV keeps moving after a step (level), oscillates, or first goes the wrong way, the FOPDT IMC/SIMC formulas give wrong settings. Check the shape of the response before calculating.

00.511.5050100150200time, sPV (normalised)self-regulating (FOPDT fits)integrating (level)oscillatory
Open-loop responses to the same output step. Only the first one has a constant final value that a first-order-plus-dead-time model can describe.

What shape the process response has

Response to an output stepProcess typeWhat to do
Moves smoothly to a new valueself-regulatingFOPDT, IMC/SIMC
Ramps at a constant rate and never stopsintegrating (level, pressure in a closed vessel)integrator-plus-delay model (below)
Almost an integrator: τ much larger than θ (τ > 8θ)lag dominantFOPDT acceptable, but Ti = 4(τc + θ) instead of τ
Oscillates on its ownoscillatory (second order)FOPDT does not fit; second-order model or careful manual tuning
First goes the opposite wayinverse response (boiler drum level)add the inverse response to θ; tune slower
Different K or τ for steps up and downnon-lineartest at several points, tune for the worst case or use gain scheduling

Half rule

For a process with several time constants (τ1 ≥ τ2 ≥ …) and dead time θ0 Skogestad proposes this FOPDT approximation: add half of the second largest time constant to τ1 and the other half to the dead time, and count the smaller time constants entirely as dead time.

τ = τ1 + τ2/2
θ = θ0 + τ2/2 + τ3 + …

Example: τ1 = 40 s, τ2 = 10 s, θ0 = 5 s → τ = 45 s, θ = 10 s.

Integrating process

Model: PV changes at a rate proportional to the output change, after a dead time θ.

dy/dt = k′ · (u(t − θ) − u0)        k′ — [PV unit / (output unit · s)]
SIMC PI:  Kc = 1 / (k′ · (τc + θ)),   Ti = 4 · (τc + θ)

Example: the level rises 0.6 %/min when the valve opens by 10 % → k′ = 0.6 / 60 / 10 = 0.001 1/s; θ = 10 s. For averaging level control choose τc = 100 s:

Kc = 1 / (0.001 · 110) = 9.09 %/%        Ti = 4 · 110 = 440 s

The tuning tool in the app handles only self-regulating FOPDT; calculate an integrating process with the formula above.

Lag-dominant process

If τ ≫ θ, IMC with Ti = τ rejects disturbances at the process input slowly: PV takes a long time to return to set point. SIMC limits Ti = min(τ, 4·(τc + θ)).

Example: K = 1.8 °C/%, τ = 400 s, θ = 12 s, τc = θ → Kc = 400 / (1.8·24) = 9.26 %/°C; Ti = min(400, 96) = 96 s, not 400 s.

Check in the tuning tool

Typical mistakes

  • Fitting FOPDT to a level: the test is cut short, the "steady" value is accidental, K and τ are meaningless.
  • Assuming θ = 0 because the response started at once: as θ → 0 the formulas give a very large Kc. Count the sample time, filter and sensor.
  • Not checking non-linearity: settings from a test at low load make the loop oscillate at high load.

Limits

The half rule and the integrator model are approximations for tuning, not exact models. Oscillatory processes and processes with strong inverse response need models and methods beyond this section.

Loading the map…

Sources

  1. Skogestad — Simple analytic rules for model reduction and PID controller tuning, J. Process Control 13 (2003) 291–309: §3 half rule, §4 integrating processes, lag-dominant processes — NTNU
  2. Åström & Murray — Feedback Systems, 2nd ed. (2020), ch. 11 «PID Control», §11.3 — Caltech / Lund University