What is Modbus
A simple request/response protocol between controllers, drives and instruments. RTU, ASCII and TCP variants, the data model and client/server terminology.
Modbus is an application-layer protocol for exchanging data between automation devices: PLCs, HMIs, variable frequency drives, meters and I/O modules. It is popular because it is simple: a client sends a request and a server returns a response or an exception. The base protocol has no subscriptions, events or typed objects.
Variants
| Variant | Physical layer | Integrity check | Typical use |
|---|---|---|---|
| Modbus RTU | RS-485, RS-232 | CRC-16 | instruments and drives on an RS-485 bus |
| Modbus ASCII | RS-485, RS-232 | LRC | rare, legacy systems |
| Modbus TCP | Ethernet, TCP port 502 | TCP/IP | PLCs, SCADA, gateways |
The application part of a message — the PDU (function code + data) — is identical in all variants. Only the wrapper (ADU) differs: RTU adds the device address and a CRC, TCP adds the MBAP header. The PDU is limited to 253 bytes, so an RTU frame is at most 256 bytes and a Modbus TCP ADU at most 260 bytes.
Client/server vs. master/slave
The serial line specification historically uses master and slave. In 2020 the Modbus Organization switched to client (initiates requests) and server (processes requests and responds). Vendor documentation uses both:
- Modbus master = Modbus client — polls devices (usually a PLC or SCADA);
- Modbus slave = Modbus server — answers requests (drive, meter, I/O module).
One RS-485 line has one client and up to 247 servers with addresses 1…247. Address 0 is reserved for broadcast write requests, which are never answered.
Data model
| Table | Element size | Access |
|---|---|---|
| Coils | 1 bit | read/write |
| Discrete Inputs | 1 bit | read-only |
| Input Registers | 16 bit | read-only |
| Holding Registers | 16 bit | read/write |
The protocol does not know what a register contains: a signed or unsigned integer, half of a FLOAT32 or a bit field. The device's register map defines the interpretation. Most practical problems come from this: off-by-one addresses and the wrong word order. See Modbus addressing and Byte and word order.
Example exchange
The client reads two holding registers starting at address 0 from device 1 (Modbus RTU):
Request: 01 03 00 00 00 02 C4 0B
│ │ └─┬─┘ └─┬─┘ └─┬─┘
│ │ │ │ CRC (low byte first)
│ │ │ quantity = 2 registers
│ │ starting address = 0 (documented as 40001)
│ function 03 Read Holding Registers
device address 1
Response: 01 03 04 42 F6 E6 66 C4 33
│ └────┬────┘
│ 4 data bytes = registers 0x42F6, 0xE666
byte count
Registers 0x42F6 0xE666 in ABCD order are the FLOAT32 value 123.45. Decode such frames with the Modbus RTU Frame Parser.
Checklist for a new device
- Protocol variant and physical layer (RTU over RS-485 or TCP).
- For RTU: baud rate, parity, stop bits, device address.
- The register map: addresses, data types, scaling, units.
- Which numbering the manual uses (0- or 1-based) and the word order of 32-bit values.