Byte and word order (ABCD, BADC, CDAB, DCBA)
Big-endian and little-endian, why a 32-bit value in two Modbus registers can be read four ways, and how to find the correct order quickly.
Endianness
Big-endian stores or transmits the most significant byte first, little-endian the least significant byte first. The number 0x12345678:
| Order | Bytes in memory / in the frame |
|---|---|
| big-endian | 12 34 56 78 |
| little-endian | 78 56 34 12 |
The Modbus specification defines big-endian only for one 16-bit register: the high byte goes first in the frame. It does not define how 32- and 64-bit values are spread over several registers — each manufacturer decides. Hence four common variants.
ABCD notation
The bytes of a 32-bit value are labelled from most to least significant: A is the highest, D the lowest. Example — FLOAT32 123.456 = 0x42F6E979 (A=42, B=F6, C=E9, D=79):
| Notation | Register 1 | Register 2 | Other names |
|---|---|---|---|
| ABCD | 42F6 | E979 | big-endian, "as is" |
| BADC | F642 | 79E9 | byte swap |
| CDAB | E979 | 42F6 | word swap — common for meters and drives |
| DCBA | 79E9 | F642 | little-endian, byte + word swap |
Finding the order on site
- Pick a parameter with a known value from the device documentation (rated frequency 50.00 Hz, a voltage, serial number, firmware version).
- Read both registers in hex.
- Enter them in the Byte / Word Order tool and pick the variant that gives a sensible result. For FLOAT32 the correct variant is usually the only one with a plausible magnitude — the others give 1e-38, 3e+21 or NaN.
- Record the order in the communication specification — for one device it is the same for all 32-bit parameters.
Signs of a wrong order:
- the value jumps while the process changes slowly — words are swapped, the low word changes faster;
- an integer value is a multiple of 65,536 — low and high words are swapped;
- small positive values turn into huge negative numbers.
Off by one register
If none of the four orders gives a meaningful number, check the address: you may be off by one (zero- vs one-based numbering), and the register pair straddles half of a neighbouring parameter. See Modbus addressing.
Tools
- Byte / Word Order — every variant for UINT32/INT32/FLOAT32 and 64-bit types.
- Modbus Data Converter — register table → values in any order.
- IEEE 754 — FLOAT32 bit breakdown.