Modbus TCP — MBAP header and gateways
How Modbus is carried over Ethernet, the MBAP header fields, port 502, the Unit Identifier and operation through Modbus TCP ↔ RTU gateways.
Modbus TCP ADU
Modbus TCP carries the application PDU (function code + data) with a 7-byte MBAP header (Modbus Application Protocol header) over TCP to port 502. There is no device address or CRC as in RTU: IP addresses the device, TCP ensures integrity.
| Field | Size | Purpose |
|---|---|---|
| Transaction Identifier | 2 bytes | transaction number; the server copies it into the response |
| Protocol Identifier | 2 bytes | always 0 for Modbus |
| Length | 2 bytes | number of following bytes, including the Unit Identifier |
| Unit Identifier | 1 byte | device address behind a gateway; copied into the response |
All fields are big-endian. Maximum ADU size is 260 bytes (7 + 253).
Example
Read two holding registers at address 0:
00 01 00 00 00 06 01 03 00 00 00 02
└─┬─┘ └─┬─┘ └─┬─┘ │ └──────┬─────┘
│ │ │ │ PDU: function 03, address 0, quantity 2
│ │ │ Unit Identifier = 1
│ │ Length = 6 (1 byte Unit ID + 5 bytes PDU)
│ Protocol Identifier = 0
Transaction Identifier = 1
The response repeats the Transaction Identifier, has Length = 7 and the PDU 03 04 xx xx xx xx.
Unit Identifier
- A device with native Modbus TCP (PLC, drive with an Ethernet option) usually ignores the Unit ID or expects a specific value — often 1, 0 or 255. Check the manual: with a wrong value some devices do not respond.
- A Modbus TCP → RTU gateway uses the Unit ID as the device address on the RS-485 line. A request with Unit ID 5 goes to device 5 on the serial bus.
Through a gateway
The gateway converts the TCP request into an RTU frame, waits for the response and returns it. Things to know:
- Response time adds TCP, the gateway queue and the RS-485 exchange; the client timeout must allow for it.
- If the device behind the gateway does not answer, the gateway may return exception 0B (GATEWAY TARGET DEVICE FAILED TO RESPOND); a routing error gives 0A.
- Serial line settings (baud rate, parity) are configured in the gateway.
Concurrent connections
A client may send several requests without waiting and match responses by Transaction Identifier, but many servers process requests one at a time and limit the number of TCP connections (sometimes 1–4). When several SCADA systems poll one device, check that limit.
Connections
Open in Knowledge Graph →Loading the map…
Sources
- MODBUS Messaging on TCP/IP Implementation Guide V1.0b — Modbus Organization
- MODBUS Application Protocol Specification V1.1b3 — Modbus Organization