Relays, contactors, circuit breakers and fuses

Switching and protection devices in control cabinets: relays vs contactors, utilization categories, coil suppression, circuit breakers and fuses, and how they interface with PLC I/O.

Relay or contactor

Relay (control relay, interface relay)Contactor
SwitchesControl circuits, small loadsMotors, heaters, power loads
ContactsLow current (≤ 10 A typ.), often changeoverMain poles for high current + auxiliary contacts
Typical useInterface between PLC outputs and other voltages, potential separationMotor starters, load switching

Utilization categories (IEC 60947) describe what a contact may switch: AC-1 resistive, AC-3 squirrel-cage motors (start, switch off running), AC-15 / DC-13 electromagnetic coils. A contact rated 10 A AC-1 may switch much less as DC-13.

Coil suppression

Switching off a coil produces a voltage spike that damages PLC transistor outputs and causes interference. Suppress at the coil:

DC coilsAC coils
Freewheeling diode (slow release!) or diode + Zener / TVS (faster)RC snubber or varistor

Many contactors offer plug-in suppressors. Check PLC output modules: some have internal suppression, which is not enough for large coils on long cables.

Circuit breakers and fuses

  • Miniature circuit breakers (MCB) protect cables against overload and short circuit; trip characteristic (B, C, D) defines the magnetic trip current (D for high inrush).
  • Fuses react fast, can protect semiconductors (gR/aR types), need replacement.
  • Motor protection circuit breakers combine short-circuit and adjustable thermal overload protection.
  • Selectivity: the protective device closest to the fault should trip first.

Interface to the PLC

  • Read the auxiliary contact of a contactor/breaker as feedback, not the PLC output.
  • Use interface relays for loads that exceed output ratings or need potential separation.
  • Feed "breaker tripped" contacts to PLC inputs for diagnostics.

Loading the map…

Sources

  1. IEC 60204-1:2016 Safety of machinery — Electrical equipment of machines — IEC
  2. SIMATIC S7-1500, ET 200MP Automation system — System Manual — Siemens AG

Updated 2026-10-02