VFD control — terminals and fieldbus

Two- and three-wire control from digital inputs, analog reference, network control via control and status words, and reference normalisation.

Terminal control

Two-wire control: one "Run" input (level). While the input is closed the motor runs; when it opens the drive stops. Simple, but after a power loss and restoration the drive may restart by itself if the input stayed closed — this must be covered by the risk assessment.

Three-wire control: momentary "Start" (NO) and "Stop" (NC) buttons. The drive latches the run state itself; opening "Stop" stops the motor. After power restoration a new start command is required.

On PowerFlex 520, for example, the mode is selected with P046 [Start Source 1] and the digital input assignments ("2-Wire", "3-Wire Start" etc.); on Siemens G120 and ABB ACS580 with setup macros and command source parameters.

A speed reference from terminals is an analog input (0–10 V, 4–20 mA), preset speeds (a combination of digital inputs) or a motor potentiometer ("up/down" inputs).

Network control

Over a network the drive receives a control word (commands) and a reference, and returns a status word and an actual value. Example — the PROFIdrive profile on Siemens G120, control word STW1:

BitMeaning
0ON / OFF1 (start / ramp stop)
1OFF2 — coast (0 = active)
2OFF3 — quick stop (0 = active)
3enable operation
4–6enable ramp generator, continue ramp, enable setpoint
7acknowledge fault (on a 0 → 1 edge)
10master control by PLC
11setpoint reversal

Hence the typical values: 16#047E — ready (OFF1, bit 0 = 0), 16#047F — run. Bit 10 must be 1, otherwise received data is not processed. The network reference is normalised: 16#4000 equals 100 % of the reference speed.

Other manufacturers use different bits (ABB, Danfoss and Rockwell have their own profiles or ODVA/DS402), but the principle is the same: command bits + reference + status word.

Network start sequence

  1. Check the status word shows no fault and the drive is ready to switch on.
  2. Send the "ready" word (e.g. 047E) and wait for "ready to operate".
  3. Send the reference and the run command (047F).
  4. Monitor the "running", "fault" and "warning" bits and supervise communication: on loss of communication the drive must go to the intended safe state (the timeout reaction parameter).

When the drive does not follow the PLC

  • Reference written in Hz or rpm directly instead of the normalised value (16#4000 = 100 %).
  • "Control by PLC" bit missing — the drive ignores commands.
  • Acknowledge sent as a level instead of an edge — the fault does not reset.
  • Byte/word order of 32-bit values over Modbus — see byte and word order.