Servo drives: how they differ from VFDs
Servo drives and motors: cascaded current, speed and position loops, encoders, tuning, homing, following error and the typical control interfaces.
What makes a servo
| VFD + induction motor | Servo drive + servo motor | |
|---|---|---|
| Motor | Asynchronous, standard | Usually permanent-magnet synchronous, low inertia |
| Feedback | Often none | Encoder always (incremental or absolute, high resolution) |
| Control | Speed (sometimes torque) | Position, speed, torque with high bandwidth |
| Typical use | Pumps, fans, conveyors | Positioning, packaging, robots, presses, axes |
Cascaded control loops
position setpoint → [position loop Kv] → speed setpoint → [speed loop Kp, Tn] → current setpoint → [current loop] → motor
↑ position feedback ↑ speed feedback (encoder) ↑ current measurement
Inner loops are faster than outer loops. Tuning starts from the inside: current loop (usually fixed by the drive), speed loop (gain and integral time against load inertia), then position loop. Many drives offer one-button or online auto-tuning.
Encoders
Incremental encoders need homing after power-up; absolute encoders (single- or multi-turn) know the position immediately. The servo motor's encoder also gives the drive the rotor position for commutation — an encoder fault stops the axis immediately (see the V90 fault list in the Diagnostic Database).
Following error
The difference between commanded and actual position. A drive monitors it against a tolerance: too small tolerance gives nuisance faults during acceleration, too large hides mechanical problems. A growing following error usually means insufficient torque, wrong tuning, mechanical binding or an encoder problem.
Control interfaces
- Pulse/direction or analog ±10 V from a motion controller (older or simple systems).
- Fieldbus telegrams: PROFIdrive (e.g. telegrams 3, 102, 105, 111 on SINAMICS), CiA 402 over CANopen/EtherCAT, CIP Motion.
- Internal positioner (basic positioner / indexing): the PLC only selects a target or a motion block.