S7 communication (S7comm, ISO-on-TCP port 102)
How HMIs, SCADA drivers and other PLCs talk to SIMATIC S7 over TCP port 102: TPKT/COTP, rack/slot and TSAP, PUT/GET access, optimised blocks and S7comm-plus.
S7 communication is Siemens' proprietary protocol used between SIMATIC S7 controllers, HMIs, SCADA drivers and engineering tools. Third-party HMIs and drivers (Weintek, Kepware, Ignition, many SCADA packages) use the classic variant often called S7comm.
Protocol stack
| Layer | Content |
|---|---|
| TCP | Port 102 (ISO-TSAP) |
| TPKT (RFC 1006) | 4-byte header that carries ISO transport over TCP |
| COTP (ISO 8073) | Connection request with TSAPs; data transfer |
| S7comm | Setup communication (PDU size), read/write variable, block functions |
The connection is addressed by IP address plus rack and slot of the CPU (encoded in the remote TSAP). Typical values: S7-300 rack 0 slot 2; S7-400 depends on the rack; S7-1200/1500 rack 0 slot 1 (the CPU accepts 0 as well in many drivers).
Access on S7-1200/S7-1500
Classic S7comm reads and writes absolute addresses (DB10.DBW4, M0.0, I/Q). On S7-1200/1500 this needs two settings in TIA Portal:
- CPU properties → Protection & Security → Permit access with PUT/GET communication from remote partner.
- For data blocks: disable Optimized block access, so the block has fixed offsets.
The engineering and HMI connections of TIA Portal use the newer S7comm-plus protocol with symbolic access and integrity protection; most third-party drivers do not speak it and rely on PUT/GET.
Security note
PUT/GET gives unauthenticated read/write access to the enabled areas. Enable it only where needed, keep the controller in a protected network segment and prefer OPC UA (S7-1500 has a built-in server) for new integrations.
Troubleshooting
- Connection refused → wrong IP/firewall, or port 102 blocked.
- Connected but "access denied"/errors on read → PUT/GET disabled or optimized DB.
- Wrong values → address offset or data type mismatch (REAL vs DINT, byte order — S7 is big-endian).