Tag naming conventions
Consistent names for equipment and signals across PLC, HMI, SCADA and documentation: instrument letter codes, structure, separators and rules that survive projects with several suppliers.
Why it matters
The same pump appears in the P&ID, the I/O list, the PLC program, HMI tags, SCADA, alarm texts, the historian and maintenance systems. If each uses a different name, every integration step needs a translation table — and errors creep in.
Instrument letter codes (ISA-5.1 style)
| Code | Meaning |
|---|---|
| PT | Pressure transmitter |
| TT / TE | Temperature transmitter / element |
| FT | Flow transmitter |
| LT | Level transmitter |
| LSH / LSL | Level switch high / low |
| PIC / TIC | Pressure / temperature indicating controller |
| XV / FV | On/off valve / flow control valve |
| M / P | Motor / pump (plant-specific) |
The first letter is the measured variable, the following letters the function; a loop number follows: PT-101, TIC-205. Many plants use KKS or another plant-specific scheme instead — follow the plant standard.
A practical structure
<area>_<equipment>_<signal>
U20_P101_Run (command)
U20_P101_RunFb (feedback)
U20_PT101_PV (process value)
U20_PT101_AlmHH (alarm)
Rules
- Same base name everywhere; only suffixes differ by signal.
- Fixed suffix vocabulary:
Cmd,Fb,PV,SP,Out,AlmH,AlmHH,Flt,Mode. - Allowed characters: letters, digits,
_— tools and protocols treat others differently (OPC UA strings, SQL, CSV). - Do not encode PLC addresses in names; addresses change.
- Keep the tag list as a single source of truth and generate PLC/HMI/SCADA tags from it where possible.