Tag naming conventions

Consistent names for equipment and signals across PLC, HMI, SCADA and documentation: instrument letter codes, structure, separators and rules that survive projects with several suppliers.

Why it matters

The same pump appears in the P&ID, the I/O list, the PLC program, HMI tags, SCADA, alarm texts, the historian and maintenance systems. If each uses a different name, every integration step needs a translation table — and errors creep in.

Instrument letter codes (ISA-5.1 style)

CodeMeaning
PTPressure transmitter
TT / TETemperature transmitter / element
FTFlow transmitter
LTLevel transmitter
LSH / LSLLevel switch high / low
PIC / TICPressure / temperature indicating controller
XV / FVOn/off valve / flow control valve
M / PMotor / pump (plant-specific)

The first letter is the measured variable, the following letters the function; a loop number follows: PT-101, TIC-205. Many plants use KKS or another plant-specific scheme instead — follow the plant standard.

A practical structure

<area>_<equipment>_<signal>
U20_P101_Run        (command)
U20_P101_RunFb      (feedback)
U20_PT101_PV        (process value)
U20_PT101_AlmHH     (alarm)

Rules

  • Same base name everywhere; only suffixes differ by signal.
  • Fixed suffix vocabulary: Cmd, Fb, PV, SP, Out, AlmH, AlmHH, Flt, Mode.
  • Allowed characters: letters, digits, _ — tools and protocols treat others differently (OPC UA strings, SQL, CSV).
  • Do not encode PLC addresses in names; addresses change.
  • Keep the tag list as a single source of truth and generate PLC/HMI/SCADA tags from it where possible.

Loading the map…

Sources

  1. ISA-101 — Human Machine Interfaces for Process Automation Systems — ISA
  2. IEC 61131-3:2025 Programmable controllers — Part 3: Programming languages — IEC