PROFIBUS troubleshooting
A practical sequence for PROFIBUS DP faults: diagnostics in the master, typical wiring errors and measurements with a multimeter before the oscilloscope.
Start in the master
The PLC diagnostic buffer and station status show which slaves fail and how: station failure (no answer), configuration fault (GSD/modules do not match), parameter fault, or device-specific diagnostics (channel errors). The standard slave diagnosis contains station status bytes, the master address and the ident number; extended diagnostics are described in the GSD.
Pattern → probable cause
| Pattern | Probable cause |
|---|---|
| All slaves behind a point fail | Terminator switched on in the middle, broken cable, unpowered active terminator |
| Random slaves fail sporadically | Reflections (missing termination), shielding, cable too long for the baud rate, spur lines |
| One slave fails | Address, GSD/configuration, device power, its connector |
| Fails only at higher baud rate | Segment too long, cable type, too many repeaters |
| Fails when a device is switched off | That device powered the terminator |
Measurements with power off
On the disconnected cable, between data lines A and B:
- ≈ 110 Ω with both terminators ON (two 220 Ω in parallel);
- ≈ 220 Ω with one terminator ON — the other end is missing;
- open circuit — no termination or broken line.
Also check A and B for short circuits to each other and to the shield, and swapped A/B wiring at a connector. Professional bus testers and oscilloscopes show signal shape and reflections when the simple checks pass.
Prevention
- Document addresses, baud rate and terminator positions on the cabinet drawing.
- Use connectors with diagnostic LEDs or test points where available.
- Route bus cables separately from power cables with the distances given in the installation guideline; bond shields to ground on both ends.